No matter what chemicals you’re storing, it’s important to conduct routine storage tank inspections. These inspections are vital to help keep the chemical tanks, fittings, venting and accessories in good working condition—and to avoid costly surprise failures. Even if the polyethylene tank is relatively new, a routine and careful visual inspection is recommended.
Even new polyethylene tanks should receive routine and careful visual inspections. Follow these inspection guidelines at least annually to help ensure the safety of personnel and the preservation of the chemical you’re storing. The tank may need to be replaced if it displays stress cracking, crazing, or embrittlement.
Poly Processing has created an annual tank inspection checklist to assist with your visual inspections. Here are a few of the basic steps—you can find a longer list in the inspection checklist in our Installation, Operation, and Maintenance manual.
NOTE: This list is not comprehensive. Your installation may require further inspection and evaluation.
WARNING: Failure to follow these inspection guidelines and take necessary corrective actions can result in unintended chemical release, causing serious property damage, injury, or even death.
Chemical fumes may be present in the area of the manway opening.
A tank is a confined space. Do not enter a tank without a confined space entry and retrieval plan.
Use lift equipment and/or fall protection to prevent fall into or away from the tank.
DO NOT STAND OR WORK ON TOP OF THE TANK. Dome surfaces are flexible and slippery. The dome may be embrittled. A dangerous fall could occur.
If you need a professional field service technician, Poly Processing can send one to your site for an additional cost. We recommend having a professional perform an in-depth inspection, with testing, periodically.
What do you get with professional tank inspection services? Here’s an overview of the inspection and testing our field service technicians perform on your chemical storage tanks.
A close inspection of the chemical tank’s exterior can reveal cracks or crazing caused by UV degradation and other stressors. If cracks are present, a field technician may scrape off a small bit of the surface of the tank to see how deep the cracks go. If they are at least 1/32” deep, further testing may be required.
As long as the tank is empty, the field technician can ultrasonically measure the tank wall thickness. This will reveal any corrosion that is eating away at the sidewall, indicating dangerous wear and tear on the tank. The technician can also insert a camera inside to take photos, which will show any degradation or interior cracking.
Download our Tank Installation Manual for instructions on do-it-yourself annual inspections.
One of the best ways to test the actual polyethylene of the storage tank is to take a sample for impact and gel testing. These tests are strong indicators of whether the tank is holding up under the stress of the chemical or if it's reaching the end of its useful life.
The ASTM-D 1998 impact test and gel test can provide an indication of the tank becoming brittle. We can take a sample from the dome and plug the tank with a bulkhead fitting, then send the sample to the lab for testing.
When a field service technician inspects your chemical tank system, they will also verify the chemical and tank compatibility. This is especially important if you have changed the chemical concentrations being stored in your tank.
Even if the structure of the tank itself seems secure, it’s important to test the fittings and attachments for signs of wear. Often, a field service representative can replace a fitting or gasket onsite. The technician will also inspect restraints, ensure seismic clips are spaced properly, and inspect ladders and brackets for signs of corrosion.
Venting is critical to the life of a tank, and it’s important to inspect the vent line for obstructions and proper vent sizing. Bird nests, beehives and other obstructions can collect in outdoor vents, and dust and other debris can collect in indoor lines.
Depending on the chemical you’re storing, you may need to inspect your tanks more frequently—especially if they are exposed to outdoor conditions. These routine, periodic tank inspections can be done by Poly technicians as well. This includes checking the following components of your chemical storage system:
All the findings from your tank inspection are presented with photo documentation and any recommendations for repairs or replacements. The report can also make a recommendation for the date of the next inspection, based on the age and condition of the tank and the chemical application.
To learn more about tank inspections and to schedule a professional tank inspection, talk to a field service expert today.